市域(郊)铁路25 kV交流接触网短路试验方法

Short-circuit Test Methods for 25 kV AC Catenary of Suburban Railways

  • 摘要:
    目的 针对市域(郊)铁路25 kV交流接触网短路试验规范化实施的迫切需求,提出一套系统化、完整的短路试验方法。
    方法 试验共选取4处具有代表性的短路点进行测试;采用R95导电线缆连接接触网与钢轨,通过断路器模拟单相接地短路故障工况;测试参数涵盖短路电压、短路电流、短路阻抗、轨道电位、芯线感应电动势等,数据采集由牵引变电所故障监测系统与短路点试验仪器协同完成,采用统计分析与图解分析相结合的方法处理数据。
    结果及结论 短路点电压最大值为19005.5~25759.1 V,电流最大值为2863.2~6000.0 A,阻抗值为1.29~2.36 Ω,短路电压、电流及阻抗均同短路点位置及过渡电阻密切相关。接触网故障点标定装置定位误差为260~1700 m,平均误差率为1.2%,具有一定定位能力但仍存在系统误差。牵引供电保护装置功能正常,各短路点保护动作时序与逻辑关系合理可靠。当持续时间不低于0.6 s时,轨道电位维持在0.1~1.7 V;当持续时间为0.1 s时,轨道电位达到最高值,各短路点轨道电位均低于评估标准限值。接触网短路产生的感应电磁场未对轨旁设施造成损伤及干扰,综合接地及电磁兼容测试结果均满足相关规范要求。

     

    Abstract:
    Objective To address the urgent need for standardized implementation of 25 kV AC catenary short-circuit testing in suburban railways, a set of systematic and comprehensive short-circuit test methods is proposed.
    Method Four representative short-circuit points are selected for testing. Connecting the catenary to the rails with R95 conductive cables, the single-phase ground fault conditions are simulated via a circuit breaker. The measured parameters include short-circuit voltage, short-circuit current, short-circuit impedance, track potential, and induced EMF (electromotive force) in core wires. Data collection is jointly completed by the fault monitoring system in the traction substation and the short-circuit point test instruments. Statistical analysis plus graphical analysis methods are used for data processing.
    Result & Conclusion The maximum short-circuit voltage at the test points ranges from 19 005.5 to 25 759.1 V, the maximum current from 2 863.2 to 6 000.0 A, and the impedance from 1.29 to 2.36 Ω. The aforementioned short-circuit voltage, current, and impedance are highly correlated with the fault location and transition resistance. The catenary fault locator exhibits a positioning error of 260 ~ 1 700 m with an average error rate of 1.2%, demonstrating a certain locating capability despite the presence of systematic errors. The traction power supply protection devices functions normally, with reasonable and reliable protection action timing and logical relationships across all points. Rail potential remains within 0.1~1.7 V when the duration is no less than 0.6 s; when the duration is 0.1 s, the rail potential reaches its peak value, with the rail potentials at each short-circuit point all below the evaluation thresholds. The induced electromagnetic field from the catenary short circuits causes no damage or interference to the wayside facilities, and the integrated grounding and electromagnetic compatibility results meet the requirements of relevant specifications.

     

/

返回文章
返回