西安地铁0.4 kV开关柜室冬季热环境实测与分析

Measurement and Analysis of Winter Thermal Environment in Xi’an Metro 0.4 kV Switchgear Room

  • 摘要:
    目的 0.4 kV开关柜室等地铁设备管理用房的空调通风系统较多存在能源浪费的现象。设备管理用房的热环境既会直接影响牵引变电等设备的稳定运行,又会影响地铁站小系统通风能耗。夏季地铁站空调系统保障其内部热环境,而冬季一般不设置空调只开启通风,导致部分时段室内温度过低,因此有必要对0.4 kV开关柜室冬季热环境进行环境实测与分析。
    方法 对西安地铁西安北站站0.4 kV开关柜室冬季热环境进行实测,收集了室内垂直梯度温度、送回风温度、风量及电气设备表面温度等信息。采用数值模拟方法,分析该0.4 kV开关柜室冬季热环境存在的问题,进而提出送风量与送回风管布局的优化方案,以温度不均匀系数等为参数分析优化结果。
    结果及结论 实测结果表明:0.4 kV开关柜室内风口风量与设计值差异明显,送回风路径受到开关柜的阻挡导致气流组织不合理。将优化方案与原方案对比发现:优化后的气流组织减少了热量堆积;温度不均匀系数由0.037降低至0.031,降低了16.2%。

     

    Abstract:
    Objective The air conditioning/ventilation system in metro equipment rooms, such as 0.4 kV switchgear room, is prone to energy waste. The thermal environment in the equipment rooms not only directly affects the stable operation of equipment such as traction substations, but also causes the ventilation energy consumption of the secondary ventilation system in metro stations. In summer, the air conditioning system ensures the internal thermal environment of the equipment rooms. However, in winter, only ventilation is operated replacing the air conditioning, which leads to excessively low indoor temperatures during certain periods. Therefore, it is necessary to conduct on-site measurement and analysis of the winter thermal environment in 0.4 kV switchgear rooms.
    Method On-site measurements of the winter thermal environment in the 0.4 kV switchgear room at Xi'an Metro North Station are conducted, and data are collected including the indoor vertical gradient temperature, supply and return air temperature, air volume, and surface temperature of electrical equipment. A numerical simulation method is adopted to analyze the problems existing in the winter thermal environment of the 0.4 kV switchgear room, and then an optimization scheme for air supply volume and the layout of supply/return air ducts is proposed. The optimization results are analyzed with parameters such as the temperature non-uniformity coefficient.
    Result & Conclusion  The on-site measurement results show that there is a significant difference between the actual air volume and design value of air outlets in the 0.4 kV switchgear room, and the supply/return air paths are blocked by switchgears, resulting in unreasonable air distribution. A comparison between the optimized scheme and the original one shows that the optimized air distribution reduces heat accumulation; the temperature non-uniformity coefficient is reduced from 0.037 to 0.031, something like a decrease of 16.2%.

     

/

返回文章
返回